TECHNICAL DATA
Power supply | 11..40 Vdc; 19..28 Vac |
Power consumption | 2 W @ 24 Vac (typical) |
Status LED indicators | Power supply Rx-Tx serial communication Link and Ethernet activity |
Communication | Nr. 2 Fast Ethernet port 100 Tx, RJ45 frontal panel (Max 8 client ModBUS TCP, Max 10 server ModBUS TCP) Nr. 1 RS232 / RS485 commutable serial port, baud rate max 115k on the connector Nr. 1 RS485, baud rate max 115k on IDC10 connector for BUS and clamps |
Industrial protocols | IEC 61850 Server ModBUS TCP-IP ModBUS RTU ModBUS ASCII MMS |
Operating modes | Gateway IEC 61850 Server ↔ ModBUS RTU Master Gateway IEC 61850 Server ↔ ModBUS TCP-IP Client |
Memory Size for variables | 512 Byte R/W |
Max N° Server TCP-IP nodes | 3 |
Max N° Slave ModBUS RTU/ASCII nodes (per serial port) | 128 |
Special functions | Advanced diagnostics Serial sniffer |
DIP switch | Yes |
Webserver | Yes, with secure authentication |
Firmware update | via Web Server |
Protection degree | IP20 |
Operating temperature | -25°C..+65°C |
Dimension (WxHxD) | 17,5 x 100 x 112 mm |
Weight | 170 g |
Housing | Nylon 6 with 30% glass fiber and V0 self-extinguishing class |
Installation | For DIN rail (IEC EN 60715) |
Standards | CE |
Norms | EN61000-6-4, EN 61000-6-2, EN 61010-1 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | Z-KEY-2ETH-I |
GROSS WEIGHT kg | 0.134 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85176200 |
ECCN | 5A991 |