TECHNICAL DATA
Power supply | 11..40 Vdc; 19..28 Vac |
Power consumption | 2 W @ 24 Vac (typical) |
Status LED indicators | Power supply Rx-Tx serial communication Link and Ethernet activity |
Communication | Nr. 1 Fast Ethernet port 100 Tx, RJ45 frontal panel (Max 8 client ModBUS TCP, Max 10 server ModBUS TCP) Nr. 1 RS232 / RS485 commutable serial port, baud rate max 115k on the connector Nr. 1 RS485, baud rate max 115k on IDC10 connector for BUS and clamps |
Industrial protocols | ModBUS TCP-IP, ModBUS RTU |
Operating modes | Modbus Gateway Ethernet to Serial (PORT#1) Modbus Gateway Ethernet to Serial (PORT#2) Modbus Gateway Ethernet to Serial (PORT#1 AND PORT#2) Modbus Gateway Serial to Ethernet (PORT#1 AND PORT#2) Modbus Tags Gateway Ethernet to Serial (PORT#1 AND PORT#2 MASTER) Modbus Tags Gateway Ethernet to Serial (PORT#1 MASTER PORT#2 SLAVE) Modbus Tags Gateway Ethernet to Serial (PORT#1 SLAVE PORT#2 MASTER) Modbus Tags Gateway Ethernet to Serial (PORT#1 AND PORT#2 SLAVE) Serial Device Server (PORT #1) Serial Device Server (PORT #2) |
Special functions | Advanced diagnostics Serial sniffer |
DIP switch | Yes |
Webserver | Yes, with secure authentication |
Firmware update | via Web Server, FTP server |
Protection degree | IP20 |
Operating temperature | -25°C..+65°C |
Dimension (WxHxD) | 17,5 x 100 x 112 mm |
Weight | 170 g |
Housing | Nylon 6 with 30% glass fiber and V0 self-extinguishing class |
Installation | For DIN rail (IEC EN 60715) |
Standards | CE |
Norms | EN61000-6-4, EN 61000-6-2, EN 61010-1 |
Handbücher, Flyer
Tools
Firmwares
ZEICHNUNGEN & CAD MODELLE
Zertifizierungen
Zubehör
Obligatorisches Zubehör, wenn Sie 2 Kommunikationsanschlüsse benötigen
Alternative Produkte
SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!
Obligatorisches Zubehör, wenn Sie 2 Kommunikationsanschlüsse benötigen
Zubehörs
Serial communication cable Z-KEY ( DB9M / MEF 10-12 )
In begrenzter Menge verfügbar ?