TECHNICAL DATA
Power supply | 11..40 Vdc 19..28 Vac |
Power consumption | 2 W (standby) 6,5 W (max) |
Insulation | 1500 Vac |
Protection degree | IP20 |
LED status | Ethernet I/O Communication (RX/TX) Power supply |
Operating temperature | -10..+50°C |
Dimensions (LxHxP) | 35x100x112 mm |
Digital inputs | N° 4 channels PNP, NPN (counters @32bit up to 30 Hz), 30 Vdc max input voltage |
Analog inputs | N° 2 channels, range 0..20 mA, 0..30 V, 16 bit |
Digital outputs | N° 2 relays output SPDT max 2 A 250 Vac |
Ethernet port | N° 1 10/100 Mbps (RJ45) |
Serial ports | N° 1 RS485 ModBUS Master, programmable baud rate N° 1 RS485/RS232, programmable baud rate via terminals |
USB interface | MicroUSB |
Modem | No |
Supported protocols | Ftp, Smtp, HTTP, ModBUS TCP, ModBUS RTU |
Programming software | SEAL 2.1 and later versions |
Backup battery | Yes (battery lasts about 60 minutes) |
On/off button | Yes |
Commands and vocal Alarms | Yes |
CPU | K64 120 MHz |
RAM | 256 kB |
Flash (program storage) | 1 MB |
Flash (serial storage) | 8 MB |
Micro SD slot | Push-pull slot. SD supports up to 32 GB |
Micro SD card | Supplied |
Data logging | Measurement, alarms, events, logging on Micro SD card (max 32 GB) or onFlash. Synchronous and asynchronous datalogger |
Libraries and features | Alarm management, commands, events, FTP/MAIL send, HTTP Log and real-time ModBUS / Ethernet variables, I/O channels, thresholds, controls, and bit operations management Firmware update and remote configuration via FTP and webserver ModBUS TCP-IP, FTP e web server, HTTP functions |
Additional features | Math functions, filters on ModBUS alarms, post/get HTTP function, blocks counter, events block |
Certification | CE |
Norms | EN 301511, EN 301489-1/7, EN 60950 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | Z-LOGGER3 |
GROSS WEIGHT kg | 0.325 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85176200 |
ECCN | 5A991 |
Manuels, prospectus
Protocole de communication RTU-Cloud (contacter notre Service & Support - supporto@seneca.it)
-
-
-
-
-
Tools
SD card contents (hw.2)
Multi
Contenu de la carte SD (audio, serveur web)
Multi
Exportation de données dans les exemples CSV
Multi
Visual syslog server for reading LOGs
Multi
Note Applicative
Comment mettre en place des calculs mathématiques Seal
Multi
Comment régler la commande de projecteur avec le calendrier astronomique
Multi
Comment copier l'état de certaines entrées d'un esclave MODBUS RTU à un autre esclave MODBUS RTU
Multi
Comment configurer l'envoi d'un onduleur Connexion sur le serveur FTP à partir d'un réseau local
Multi
Comment régler la distribution des alarmes chez les utilisateurs
Multi
Firmwares
DESIGNS & CAD MODÈLES
Certifications
Accessoires
Accessoire obligatoire si vous avez besoin de 2 ports de communication
Produits Liés
Produits alternatifs
Versions du produit
Prix
€ 360,00
Accessoire obligatoire si vous avez besoin de 2 ports de communication
Prix
€ 23,00
€ 21,00
€ 32,00
Accessoires
Prix
€ 18,00
€ 14,00
€ 7,00
CU-A-MICROB
USB cable plug USB-A - MicroUSB-B - 5P ( KIT - USB , MY2 , Z109REGBP )
Disponible en quantité limitée ?
€ 7,00
€ 74,00
€ 33,00