TECHNICAL DATA

Precision Class 0.5
Transformation Ratio depending on the model:
100/5
150/5
200/5
250/5
300/5
400/5
Nominal performance 1.5 VA
Secondary current 5A
Frequency 40-60 Hz
Nominal dynamic DC 2.5 I.ter@1s
Nominal thermal current dc 40-80 IpN@1s
Reference voltage 0.72 kV
Test voltage 3kV@50Hz (1 min)
Permanent overcurrent 1.2 In
Safety Factor (FS) =<5
Temperature of use -25..+50°C
Storage temperature -40..+80°C
Max. through-wire temperature 70°C
Relative humidity 90% non-condensing
Isolation in air Class E
Protection class IP30 (CEI EN 60529)
Container Self-extinguishing ABS, protected terminals
Installation type DIN rail
Hole size 20x30 mm
Dimensions 89x111x40 mm
Weight 720 g
Reference standards CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A

Manuales, flyer

 
IT EN
Datasheet
pdf icon it pdf icon en

Certificados

 
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!

Versiones del producto

Precio
TAA-01005-2030

Split core current transformer 100/5A CL.0,5 D=20x30mm

Disponibilidad para confirmar, contáctenos ?
111,00
TAA-01505-2030

Split core current transformer 150/5A CL.0,5 D=20x30mm

Disponibilidad para confirmar, contáctenos ?
111,00
TAA-02005-2030

Split core current transformer 200/5A CL.0,5 D=20x30mm

Disponibilidad para confirmar, contáctenos ?
111,00
TAA-02505-2030

Split core current transformer 250/5A CL.0,5 D=20x30mm

Disponible en cantidad limitada ?
114,00
TAA-03005-2030

Split core current transformer 300/5A CL.0,5 D=20x30mm

Disponibilidad para confirmar, contáctenos ?
114,00
TAA-04005-2030

Split core current transformer 400/5A CL.0,5 D=20x30mm

Disponibilidad para confirmar, contáctenos ?
114,00