TECHNICAL DATA

Precision Class 0.5
Transformation Ratio depending on the model:
100/5
150/5
200/5
250/5
300/5
400/5
Nominal performance 1.5 VA
Secondary current 5A
Frequency 40-60 Hz
Nominal dynamic DC 2.5 I.ter@1s
Nominal thermal current dc 40-80 IpN@1s
Reference voltage 0.72 kV
Test voltage 3kV@50Hz (1 min)
Permanent overcurrent 1.2 In
Safety Factor (FS) =<5
Temperature of use -25..+50°C
Storage temperature -40..+80°C
Max. through-wire temperature 70°C
Relative humidity 90% non-condensing
Isolation in air Class E
Protection class IP30 (CEI EN 60529)
Container Self-extinguishing ABS, protected terminals
Installation type DIN rail
Hole size 20x30 mm
Dimensions 89x111x40 mm
Weight 720 g
Reference standards CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A

Handbücher, Flyer

 
IT EN
Datasheet
pdf icon it pdf icon en

Zertifizierungen

 
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!

Produktversionen

Preis
TAA-01005-2030

Split core current transformer 100/5A CL.0,5 D=20x30mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
111,00
TAA-01505-2030

Split core current transformer 150/5A CL.0,5 D=20x30mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
111,00
TAA-02005-2030

Split core current transformer 200/5A CL.0,5 D=20x30mm

In begrenzter Menge verfügbar ?
111,00
TAA-02505-2030

Split core current transformer 250/5A CL.0,5 D=20x30mm

In begrenzter Menge verfügbar ?
114,00
TAA-03005-2030

Split core current transformer 300/5A CL.0,5 D=20x30mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
114,00
TAA-04005-2030

Split core current transformer 400/5A CL.0,5 D=20x30mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
114,00