TECHNICAL DATA
Electrical Protection Data (L-N / N-PE / L-PEN) | |
IEC test class / EN type | III / T3 |
Rated voltage UN | 24 Vac (TN-S) |
Max. permanent voltage UC | 34 Vac |
Rated leakage current In (8/20)µs | 1 kA |
Max. Leakage current Imax (8/20)µs | 1 kA |
Rated load current IL | 16 Aac (@63°C); 10 Adc |
Protection Level Up | ≤ 0.18 kV (L-N) / ≤ 0.55 kV (L-PE) / ≤ 0.55 kV (N-PE) |
Combination wave Uoc | ≤ 25 ns |
Intervention time tA | L-N ≤ 25 ns / L-PE ≤ 100 ns / N-PE ≤ 100 ns |
General Data | |
Max. fuse for standard wiring | 16 Aac - 10 Adc |
Dimensions (wxhxd) | 17.7 x 90 x 65.5 mm |
Temperature range | -40°C to +80°C |
Grade of Protection | IP20 |
Combustibility Class by UL 94 | V0 |
Casing material | PA 6.6 |
Connection interface | Screw connection |
Approvals | CE |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400LV-1-N |
GROSS WEIGHT kg | 0.105 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |