TECHNICAL DATA

Electrical Protection Data (L-N / N-PE / L-PEN)  
IEC test class / EN type III / T3
Rated voltage UN 24 Vac (TN-S)
Max. permanent voltage UC 34 Vac
Rated leakage current In (8/20)µs 1 kA
Max. Leakage current Imax (8/20)µs 1 kA
Rated load current IL 16 Aac (@63°C); 10 Adc
Protection Level Up ≤ 0.18 kV (L-N) / ≤ 0.55 kV (L-PE) / ≤ 0.55 kV (N-PE)
Combination wave Uoc ≤ 25 ns
Intervention time tA L-N ≤ 25 ns / L-PE ≤ 100 ns / N-PE ≤ 100 ns
General Data  
Max. fuse for standard wiring 16 Aac - 10 Adc
Dimensions (wxhxd) 17.7 x 90 x 65.5 mm
Temperature range -40°C to +80°C
Grade of Protection IP20
Combustibility Class by UL 94 V0
Casing material PA 6.6
Connection interface Screw connection
Approvals CE

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE S400LV-1-N
GROSS WEIGHT kg 0.105
ORIGIN DE
CN (Combined Nomenclature) 85363030
ECCN EAR99