TECHNICAL DATA
Power supply | 11..40 Vdc; 19..28 Vac |
Power consumption | 2 W @ 24 Vac (typical) |
Status LED indicators | Power supply Rx-Tx serial communication Link and Ethernet activity |
Communication | Nr. 2 Fast Ethernet port 100 Tx, RJ45 frontal panel (Max 8 client ModBUS TCP, Max 10 server ModBUS TCP) Nr. 1 RS232 / RS485 commutable serial port, baud rate max 115k on the connector Nr. 1 RS485, baud rate max 115k on IDC10 connector for BUS and clamps |
Industrial protocols | ModBUS TCP-IP, ModBUS RTU, ModBUS ASCII |
Operating modes | Modbus Gateway Ethernet to Serial (PORT#1) Modbus Gateway Ethernet to Serial (PORT#2) Modbus Gateway Ethernet to Serial (PORT#1 AND PORT#2) Modbus Gateway Serial to Ethernet (PORT#1 AND PORT#2) Modbus Tags Gateway Ethernet to Serial (PORT#1 AND PORT#2 MASTER) Modbus Tags Gateway Ethernet to Serial (PORT#1 MASTER PORT#2 SLAVE) Modbus Tags Gateway Ethernet to Serial (PORT#1 SLAVE PORT#2 MASTER) Modbus Tags Gateway Ethernet to Serial (PORT#1 AND PORT#2 SLAVE) Serial Device Server (PORT #1) Serial Device Server (PORT #2) |
Special functions | Advanced diagnostics Serial sniffer |
DIP switch | Yes |
Webserver | Yes, with secure authentication |
Firmware update | via Web Server, FTP server |
Protection degree | IP20 |
Operating temperature | -25°C..+65°C |
Dimension (WxHxD) | 17,5 x 100 x 112 mm |
Weight | 170 g |
Housing | Nylon 6 with 30% glass fiber and V0 self-extinguishing class |
Installation | For DIN rail (IEC EN 60715) |
Standards | CE |
Norms | EN61000-6-4, EN 61000-6-2, EN 61010-1 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | Z-KEY-2ETH |
GROSS WEIGHT kg | 0.13 |
ORIGIN | IT |
CN (Combined Nomenclature) | 85176200 |
ECCN | 5A991 |
Manuels, prospectus
Tools
![zip icon](/assets/images/icons/ZIP.png)
Firmwares
DESIGNS & CAD MODÈLES
Certifications
Accessoires
Accessoire obligatoire si vous avez besoin de 2 ports de communication
Produits alternatifs
SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!
Versions du produit
Accessoire obligatoire si vous avez besoin de 2 ports de communication
Accessoires
Serial communication cable Z-KEY ( DB9M / MEF 10-12 )
Disponibilité à confirmer, nous contacter ?