TECHNICAL DATA
Precision Class | 0.5 |
Transformation Ratio | depending on model 20/5 25/5 30/5 |
Nominal performance | 3 VA |
Secondary current | 5A |
Frequency | 40-60 Hz |
Nominal dynamic DC | 2.5 I.ter@1s |
Nominal thermal current dc | 40-80 IpN@1s |
Reference voltage | 0.72 kV |
Test voltage | 3kV@50Hz (1 min) |
Permanent overcurrent | 1.2 In |
Safety factor (FS) | =<5 |
Temperature of use | -25..+50°C |
Storage temperature | -40..+80°C |
Relative humidity | 90% non-condensing |
Isolation in air | Class E |
Protection class | IP30 (CEI EN 60529) |
Container | Self-extinguishing ABS, sealable terminal covers |
Installation type | DIN rail |
Pole dimensions | 6 mm |
Dimensions | 47x56x84 mm |
Weight | n.a. |
Reference standards | CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A |
Manuales, flyer
Certificados
Productos relacionados
SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!
Versiones del producto
Primary wound current transformer 25/5A CL. 0.5
Disponibilidad para confirmar, contáctenos ?Primary wound current transformer 30/5A CL. 0.5
Disponibilidad para confirmar, contáctenos ?