TECHNICAL DATA

Precision Class 0.5
Transformation Ratio depending on model
500/5
800/5
1000/5
Nominal performance 1.5 VA
Secondary current 5A
Frequency 40-60 Hz
Nominal dynamic DC 2.5 I.ter@1s
Nominal thermal current dc 40-80 IpN@1s
Reference voltage 0.72 kV
Test voltage 3kV@50Hz (1 min)
Permanent overcurrent 1.2 In
Safety Factor (FS) =<5
Temperature of use -25..+50°C
Storage temperature -40..+80°C
Max. through-wire temperature 70°C
Relative humidity 90% non-condensing
Isolation in air Class E
Protection class IP30 (CEI EN 60529)
Container Self-extinguishing ABS, protected terminals
Installation type DIN rail
Hole size 80x80 mm
Dimensions 144x145x82 mm
Weight 1005 g
Reference standards CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A