TECHNICAL DATA

Precision Class 1
Transformation Ratio 50/5
Nominal power output 1 VA
Secondary current 5A
Frequency 40-60 Hz
Nominal dynamic DC 2.5 I.ter@1s
Nominal thermal current dc 40-80 IpN@1s
Reference voltage 0.72 kV
Test voltage 3kV@50Hz (1 min)
Permanent overcurrent 1.2 In
Safety factor (FS) =<5
Temperature of use -25..+50°C
Storage temperature -40..+80°C
Max. through-wire temperature 70°C
Relative humidity 90% non-condensing
Isolation in air Class E
Protection class IP30 (CEI EN 60529)
Container Self-extinguishing ABS, sealable terminal covers
Installation type DIN rail
Hole dimensions 22 mm (cable), 30x10 mm (bar)
Dimensions 46x57x83.5 mm
Weight n.a.
Reference standards CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A

Handbücher, Flyer

 
TAC
TAC
jpg icon Multi

Zertifizierungen

 
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!

Produktversionen

Preis
TAC-0505-22-3010

Through-bar current transformer 50/5A CL.1, cable 22mm, bar 30x10mm

Auf Lager ?
19,00
TAC-0605-22-3010

Through-bar current transformer 60/5A CL.1, cable 22mm, bar 30x10mm

Auf Lager ?
20,00
TAC-01005-22-3010

Through-bar current transformer 100/5A CL.1, cable 22mm, bar 30x10mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
20,00
TAC-01505-22-3010

Through-bar current transformer 150/5A CL.1, cable 22mm, bar 30x10mm

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
20,00