TECHNICAL DATA
Precision Class | 0.5 |
Transformation Ratio | depending on model 250/5 400/5 500/5 600/5 750/5 800/5 |
Nominal performance | 1.5 VA |
Secondary current | 5A |
Frequency | 40-60 Hz |
Nominal dynamic dc current | 2.5 I.ter@1s |
Nominal thermal current dc | 40-80 IpN@1s |
Reference voltage | 0.72 kV |
Test voltage | 3kV@50Hz (1 min) |
Permanent overcurrent | 1.2 In |
Safety Factor (FS) | =<5 |
Temperature of use | -25..+50°C |
Storage temperature | -40..+80°C |
Max. through-wire temperature | 70°C |
Relative humidity | 90% non-condensing |
Isolation in air | Class E |
Protection class | IP30 (CEI EN 60529) |
Container | Self-extinguishing ABS, protected terminals |
Installation type | DIN rail |
Hole size | 50x80 mm |
Dimensions | 114x145x82 mm |
Weight | 900 g |
Reference standards | CEI 38-1, IEC 185, VDE 0414, EN600044-1, EN60044-1A |
Handbücher, Flyer
Zertifizierungen
Ähnliche Produkte
SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!
Produktversionen
Split core current transformer 250/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?Split core current transformer 400/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?Split core current transformer 500/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?Split core current transformer 600/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?Split core current transformer 750/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?Split core current transformer 800/5A CL.0,5 D=50x80mm
Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?