Code: |
S400CL-1 |
Description: |
Overvoltage protection for analog signals and logical with isolator |
IEC category / VDE requirement class |
C1, C2, C3, D1 |
Max. perm. operating voltage UC |
30 VDC / 21 VAC |
Lightning test current Iimp (10/350) μs - Core - ground |
500 A |
Nominal current IN |
300 mA (40 °C) |
Backup fuse max. |
315 mA |
Nominal discharge surge current In (8/20) μs - Core – core / core - ground |
5 kA / 5 kA |
Total surge current (8/20) μs - Core – ground |
10 kA |
Output voltage threshold at 1 kV / μs - Core – core / core – ground |
≤ 45 V / ≤ 650 V |
Residual voltage at In core - core |
≤ 45 V |
Protection level UP C2 ( 10kV / 5 kA ) - Core – core / core – ground |
≤ 55 V / ≤ 650 V |
Response time TA Core – core / core - ground |
≤ 1 ns / ≤ 100 ns |
Cut-off frequency (3dB) symmetrical in a 150 Ω system |
typ. 2 MHz |
Resistance per path |
3,3 Ù ±20% |
Temperature range |
-40 °C…+85 °C |
Inflammability class according to UL 94 |
V0 |
Degree of protection with IEC 60529 / EN 60529 |
IP20 |
Test standards |
IEC 61 643-21:2002-03 |
Connection data (solid / stranded / AWG) |
0,2 mm² - 2,5 mm² / 0,2 mm² - 2,5 mm² / 24-12 |
Screw thread / tightening torque |
M3 / 0,6 Nm |
Stripping length |
8 mm |
Surge voltage category |
III |
Pollution degree |
2 |