TECHNICAL DATA
Power supply | 11 - 28 Vdc |
Max absorption | Typical: < 70 mA @ 24 Vdc |
Isolation | 3 kVac (on bare wires) |
Status indicators | Power supply, USB communication, digital output |
Installation category/overvoltage | CAT. III 600V (bare conductor) CAT. III 1kV (insulated conductor) |
Frontal protection class | IP20 |
Mounting | DIN 35mm IEC EN60715 rail, wall-mounted using dowels, suspended using cable ties |
Connections | 6-way removable screw terminals, 5 mm pitch for cables up to 2.5 mm2 |
Micro USB for programming and fw upgrade | |
Operating temperature | -25..+65°C |
Dimensions | 95 x 75 x 35 mm |
Weight | 150 g |
Case | PA6, colour black |
Measuring and calculating templates | |
Sampling time | 47,000 sps |
Settling time RMS values | 500..1000 ms (up to 99.5%) |
MEASURED PARAMETERS | |
Instantaneous values | Voltage, AC/DC Current, Active / Reactive / Apparent Power, Power Factor, Frequency, THD |
Average / max / min values | Voltage, AC/DC Current, Active / Reactive / Apparent Power, Power Factor, Frequency, THD |
Harmonics | Up to 21th |
Precision class | 0,5% f.s. @ 50/60 Hz, 23°C (above 2% f.s.) 1% f.s. @ 50/60 Hz, 23°C (above 2% f.s.) |
COMMUNICATION | |
Serial interface | N°1 RS485 port |
Protocol | ModBUS RTU |
Distance | Up to 1,200 m |
Connectivity | Max 32 modes |
Port | N°1 Micro USB programming port |
METERING INPUTS | |
Voltage / Current | Up to 0..600 A or 0..290 Vac (AC/DC TRMS); 0..1000 Vdc TRMS DC Bipolar Crest factor: 100A = 1.7 / 300A = 1.9 / 600A = 1.9 Passband: 1.4 kHz Overload: 3 x IN continuous |
BUILT-IN I/O | |
Channels | 1DO, 1AO |
Digital output | ACTIVE 0 - Vdc, max. load 50mA |
Analog output | Voltage: 0..10 Vdc, minimum load 2kΩ. Reverse polarity and overvoltage protection Resolution: 13.5 f.s.AC Error for EMI: < 1 % Coeffic. Temperature: < 200 ppm/°C Hysteresis on measurement: 0.2% f.s. Response time: < 200 ms |
Programming | EASY SETUP 2 |
Certifications/Markings | CE |
Standards | EN61000-6-4, EN61000-6-2, EN61010-1 |
Product versions
Price