TECHNICAL DATA

Power supply 3 V
Battery type and lifetime Lithium, 900 mAh, max. indicative duration 1 year
Protection degree IP20
Status LED Sending / Receiving Data from / to R-GWR
Operating temperature -25..+70°C
Storage temperature -40..+85°C
Humidity 10% to 90% non-condensing
Dimension (WxHxD) 65 x 45 x 30 mm
Weight 45 g
Container PC / ABS material self-extinguishing UL94-V0
Connections Screw terminals, removable 2-way screw, 3.5 mm pitch
Flood-proof probe connector
Mounting Wall mounting by means of screws or double-sided adhesive tape
Programming Web Server
Button for pairing
Regulations ETSI EN 301 489-1 v.2.2.3, ETSi EN 301 409-3 v.2.1.1, EN 60950, ETSI 300 220-2 v3.2.1
RADIO COMMUNICATION  
Technology LoRa
Frequency Band 863..865 MHz
Nominal Frequency 863.11 MHz
Bandwidth 25 kHz
Sensitivity Up to -146 dBm
Max RF Power +14 dBm
Max No. of coupled sensors 32
INPUT CHANNELS  
Integrated Temperature/Humidity Sensor Temperature detection: -25..70 °C, Accuracy: 0,5 °C between 5..60 °C
Humidity detection: 0..100%, Accuracy: 3% between 20 ÷ 80% R.H.
Analog/digital inputs It is possible to set the input channel with one of the following options:
- Nr.1 Analog input 0..30V (accuracy ±0.15 V) or Nr.1 Digital Input/counter
- Nr.1 Digital input Reed relay for the control of the opening of compartments or doors
as an alternative to the described input channels
- Nr.1 Digital input for anti-flooding probe contact (see accessory)
Counter @16bit, max frequency 1Hz
Anti-tamper function Yes

 
IT EN FR DE ES
Datasheet
pdf icon it pdf icon en - - -
Sensor Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es

 
CE Declaration of Conformity
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

Product versions

R-GWR-S-1

LoRa Wireless Sensor (civil environment) for R-GWR Radio Hub

?


R-GWR-AF

Anti-Flooding sensor cable

?