TECHNICAL DATA

Power supply 12..28 Vdc
Absorption 38 mA excluding load
Isolation and protections 3 kVac (on bare conductors)
Front LED Power supply
USB/RS485 communication
Digital output
Overvoltage Category 300 V CAT III (bare conductor);
600 V CAT III (insulated conductor)
Polarity of measurement Positive (label-side incoming current)
Configuration and data export DIP Swtich, Software (EASY SETUP)
Grade of Protection IP20
Precision class 0.5% f.s. (DC bipolar, AC TRMS)
Operating temperature -25..+70°C
Storage temperature -40..+85°C
Humidity 10rH..90% non-condensing
Altitude Up to 2,000 m above sea level
Nucleus Apensible
Connections 5-way removable screw terminals, 5mm pitch for cables up to 2.5mm2
Through-hole diameter 35 mm
Dimensions (WxHxD) 95x75x35 mm
Mounting 35mm DIN rail IEC EN60715 or fixing by plastic ties.
Container PA6, color black
Weight 145 g
Certifications CE, UKCA
COMMUNICATION  
Communication Port RS485 / USB
Protocol ModBUS RTU slave
Speed 1,200..115200 bps
INPUT DATA  
Channels 1
Range 0-150/300/600 Aac/dc TRMS;
±300/300 Adc Bipolar
Type of Measurement AC/DC TRMS or DC Bipolar
Bipolar Measurement Yes
Hysteresis 0.2% f.s.
Overloading 3xIIN continuous;
2,000 A (impulsive)
Bandwidth 1 kHz
Crest Factor 2
OUTPUT DATA  
Channels analogous 1
Range 0..10 V
Resolution 13 bits (10,000 points)
Max Load 2 kOhm
Error for EMI 0.5%
Thermal Drift 200 ppm/K
Response Time Fast filter: 800 ms
Slow filter: 2 s
Digital Channels 1
Function Alarm (as an alternative to analog channel)
Type PNP active output, 50 mA max
DIMENSION CONDUCTORS  
Max cable section 300 mm2
Max cable diameter 33 mm (FG16R16)
Max through bar size 2 32x5 mm bars coupled with max capacity 695 A (ΔT 30°C) or 920 A (ΔT 50°C)

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE T201DCH600-OPEN
GROSS WEIGHT kg 0.19
ORIGIN IT
CN (Combined Nomenclature) 85437090
ECCN EAR99

Manuales, flyer

 
IT EN FR DE ES
Transductores de corriente Serie T201
pdf icon it pdf icon en - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es
User Manual
pdf icon it pdf icon en - - -

DISEÑOS Y MODELOS CAD

 
3D Model
zip icon Multi

Certificados

 
Declaración de Conformidad
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!

Versiones del producto

Precio
T201DCH600-OPEN

AC/DC current transformer (± 600 A) openable with Hall effect TRMS with 0.10 V output

En stock ?
149,00