TECHNICAL DATA

Order code : K109TC
Description: Thermocouple converter with settable threshold
Input: Thermocouple type B,E,J,K,R,S,T,N (ITS-90), min span 100 °C
Output: current 0/4..20, 20..4/0 mA; voltage 0..5/10, 10..0, 1..5 Vdc
Power Supply: 19,2..30 Vdc
Auxiliary output: SSR for settable alarm trip
Max consumption: 24 mA
Insulation: 1,5 kVac, 3 way
Resolution: 14 bit
Precision class: 0,1%
Power supply technique: direct on spring cage terminale or distributed with K-BUS connector
Dimensions: 6,2 x 93,1 x 102,5 mm

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE K109TC
GROSS WEIGHT kg 0.075
ORIGIN IT
CN (Combined Nomenclature) 85437090
ECCN EAR99

Manuales, flyer

 
IT EN FR DE ES RU
Hoja de Datos
pdf icon it pdf icon en - - - -
Convertidores compacto K line
pdf icon it pdf icon en - - - -
Application Scheme
pdf icon it - - - - -
Application Note
- pdf icon en - - - -

DISEÑOS Y MODELOS CAD

 
2D model
dwg icon Multi
Modelo 3D
dwg icon Multi
Los símbolos eléctricos modelo 3D
dwg icon Multi
3D Model
stp icon Multi

Certificados

 
Declaración de Conformidad
pdf icon Multi
UL Certification
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

Versiones del producto

Precio
K109TC

TC to DC current/voltage isolator converter (with trip alarm)

En stock ?
135,00

Aaccesorios

Precio
K-SUPPLY

Redundant power supply module for K-Line modules

En stock ?
58,00
K-BUS

Expandable power supply connector

Disponibilidad para confirmar, contáctenos ?
11,00
K-BUS-G

Expandable power supply connector

En stock ?
11,00
K-BUS-V

Expandable power supply connector

Disponibilidad para confirmar, contáctenos ?
11,00