TECHNICAL DATA
Protection Electrical Data (L-N / N-PE / L-PEN) | |
IEC test class / EN type | C1 / C2 / C3 / D1 |
Rated voltage UN | 24 Vdc |
Max. permanent voltage UC | 30 Vdc / 21 Vac |
Rated leakage current In (8/20)µs | 5 kA |
Max. Leakage current Imax (8/20)µs | 20 kA |
Atmospheric test current Iimp (10/350) µs per conductor | 0.5 kA |
Protection Level Up | (conductor-to-conductor) ≤ 55 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) ≤ 50 V (C3 - 25 A) (conductor-to-ground) ≤ 55 V (C3 - 100 A) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) ≤ 700 V (C3 - 25 A) ≤ 750 V (C3 - 100 A) (conductor-ground) ≤ 50 V (C1 - 1 kV / 500 A) ≤ 65 V (C2 - 10 kV / 5 kA) (conductor-ground) ≤ 750 V (C1 - 1 kV / 500 A) ≤ 750 V (C2 - 10 kV / 5 kA) |
General Data | |
Max. fuse for standard wiring | 630 mA (FF) |
Frequency limit fg (3dB) symmetrical in 50 Ohm system | tip. 940 kHz |
Resistance per conductor | 1.65 Ohm ±20 % |
Dimensions (wxhxd) | 6.2 x 105 x 83 mm |
Temperature range | -40..+70°C |
Grade of Protection | IP20 |
Combustibility Class by UL 94 | V0 |
Casing material | PBT |
Connection interface | Connection push-in |
Approvals | CE |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400CL-1-N |
GROSS WEIGHT kg | 0.105 |
ORIGIN | DE |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |