LoRa technology ensures low power consumption, longer battery life, lower power involved, and reduced installation costs and sensors. The communication range is dependent on the conditions of use, however, LoRa ensures a deep penetration in urban, rural, or indoor areas up to reach ranges of 500 meters. The minimum update interval of the measured values is 30 seconds.

The device is easily programmable via a DIP switch and web server. The main applications concern the remote transmission of industrial and civil measurements and monitoring production sites, environments, and industrial and residential buildings.

TECHNICAL DATA

Power Supply 10..40 Vdc; 19..28 Vac
Power consumption Max 1 W
Battery type and lifetime Lithium with variable autonomy from 12 to 36 months
Status Indicators Power supply
Rx-Tx serial communications
Sensors assigned
Sensors in error
Protection degree IP20
Operating temperature -20..+70°C
Connections Screw terminals, removable 7-way screw, 5mm pitch
Screw terminals, removable 2-way screw, 5mm pitch
Ethernet connector
Communication Nr 1 Fast Ethernet 100 Tx port, RJ45 front. 
Nr 1 RS232 / RS485 serial port switchable, baud rate max 115k on connector
Connectivity Up to 8 TCP-IP Clients
Supported protocols ModBUS TCP-IP server
ModBUS RTU slave
Dimension (WxHxD) 53.3 x 90 x 32.2 mm
Weight 80 g
Housing PC / ABS self-extinguishing UL94-V0
Installation On IEC EN 60715 DIN rail or wall-mounted
Certification CE
Standards ETSI EN 301 489-1 v.2.2.3, ETSi EN 301 409-3 v.2.1.1, EN 60950
WIRELESS  
Radio Technology LoRa
Minimum Measurement Interval 30 seconds
Security AES 128bit
Frequency Frequency Band: 863-865 MHz,
Nominal Frequency: 863.110 MHz,
Bandwidth 25 KHz,
Max Power +14 DBm
Sensitivity Up to -146 dBm
Power +14 dBm
Max Number of coupled sensors 32
SETTINGS & ADVANCED FUNCTIONS  
DIP switch Yes
Webserver Yes
SDD (Seneca Discovery Device) Yes
Firmware Update via Web Server
Advanced Diagnostics Yes

Manuals, flyers

 
IT EN FR DE ES
Datasheet
pdf icon it pdf icon en - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es
User Manual
pdf icon it pdf icon en - - -

Firmwares

 
IT EN
Firmware SW01180-1.2.3.0 (please read release notes .txt)

SHA256 Checksum:
656d543c58874668e52b340918125c736fa2e4cf1a032ae2d74d566e065489f3
zip icon Multi txt icon it txt icon en
Firmware SW01180-1.0.0.22 (please read the release notes)

SHA256 Checksum:
0e3988e1018a3ed2ef90e004fd59d0af301f15d65b91394d61b3ea0e5bbf2fb7
zip icon Multi txt icon it txt icon en

Certifications

 
CE Declaration of Conformity
pdf icon Multi
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
0
0
0

SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!

Product versions

Price
R-GWR

ModBUS Gateway / Radio Hub LoRa for wireless sensors

In stock ?
320.00

Accessories

Price
A-GSM-MG

External Antenna for Z-LINK Series Radio Modules

In stock ?
20.00
R-GWR-IP-1

LoRa Wireless Sensor (industrial environment)

Limited quantity available ?
160.00
R-GWR-IP-2

LoRa Wireless Sensor (industrial environment) with XL battery pack

Limited quantity available ?
180.00
R-GWR-S-1

LoRa Wireless Sensor (civil environment) for R-GWR Radio Hub

In stock ?
160.00