TECHNICAL DATA
Code | S400HV-2 |
Description | Type 2 surge arrester for power lines |
IEC category / EN type | II , T2 / T2 |
Number of ports | 1 |
Nominal voltage UN AC | 240/415 VAC (TN-S) / 240/415 V AC (TT) |
Maximum continuous operating voltage UC - L-N / N-PE | 335 V AC / 260 V AC |
Residual current IPE | ≤ 5 μA |
Short-circuit current rating ISCCR | 25 kA |
Follow current interrupt rating Ifi - N-PE | 100 A (260 V) |
Max. discharge surge current Imax (8/20)μs - L-N / N-PE | 40 kA / 40 kA |
Voltage protection level UP L-N / N-PE | ≤ 1,5 kV / 1,5 kV |
Nominal discharge surge current In (8/20)μs - L-N / N-PE | 20 kA / 20 kA |
Max. required backup fuse with branch wiring | 125 A AC (gG) |
Max. required backup fuse with V-type through wiring | 80 A AC (gG) |
Ambient temperature (operation) | -40 °C ... 80 °C |
Permissible humidity (operation) | 5 % ... 95 % |
Degree of protection | IP 20 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400HV-2 |
GROSS WEIGHT kg | 0.105 |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |