TECHNICAL DATA
Code | S400HV-2 |
Description | Type 2 surge arrester for power lines |
IEC category / EN type | II , T2 / T2 |
Number of ports | 1 |
Nominal voltage UN AC | 240/415 VAC (TN-S) / 240/415 V AC (TT) |
Maximum continuous operating voltage UC - L-N / N-PE | 335 V AC / 260 V AC |
Residual current IPE | ≤ 5 μA |
Short-circuit current rating ISCCR | 25 kA |
Follow current interrupt rating Ifi - N-PE | 100 A (260 V) |
Max. discharge surge current Imax (8/20)μs - L-N / N-PE | 40 kA / 40 kA |
Voltage protection level UP L-N / N-PE | ≤ 1,5 kV / 1,5 kV |
Nominal discharge surge current In (8/20)μs - L-N / N-PE | 20 kA / 20 kA |
Max. required backup fuse with branch wiring | 125 A AC (gG) |
Max. required backup fuse with V-type through wiring | 80 A AC (gG) |
Ambient temperature (operation) | -40 °C ... 80 °C |
Permissible humidity (operation) | 5 % ... 95 % |
Degree of protection | IP 20 |
SHIPPING AND EXPORT INFORMATION
PRODUCT CODE | S400HV-2 |
GROSS WEIGHT kg | 0.105 |
CN (Combined Nomenclature) | 85363030 |
ECCN | EAR99 |
Handbücher, Flyer
Zertifizierungen
Zubehör
SENECA offices will be closed from August 3 to August 25 included. Business activities will resume regularly on Monday 26 August. Orders received from July 30 will be shipped from August 26. We wish you happy summer holiday!
Produktversionen
Zubehörs
Replacement plug 1 LN / PE S400HV-2, no contact FMII / T2 335Vac / 260Vac
In begrenzter Menge verfügbar ?Replacement plug N / per S400HV2 II / T2 335 VAC / 260 VAC / -335 Vac / 260Vac
In begrenzter Menge verfügbar ?