TECHNICAL DATA

Power supply 10..40 Vdc, 19..28 Vac (@50..60 Hz)
Power consumption 2 W
Insulation 1.500 Vac a 3 vie
Accuracy class 0,01%
Status LED Power supply
Error
Tx Data
Rx Data
Input channels 1 analog channel for reading (and power supply) up to 4 (350 Ω) or 8 (1,000 Ω) strain gauge load cells, 4 or 6-wire connection, equivalent impedance 87 Ω
1DI tare calibration or weight threshold
Output channels 1 analog retransmission channel of the net weight in current (0...20, 4...20 mA) or in voltage (0..5, 0..10 V);
1DO tare calibration or weight threshold
Advanced features Tare acquisition
Stable weighing signaling via Modbus
Tara Silos function
Counting function
Tare reset function
Datalogging on EASY Setup
Advanced settings Analog output with programmable limits
Upgradeable firmware
I/O independent digital
Wide-range settable sampling rate
Alarm threshold with programmable hysteresis
Fully configurable analog output
Configurable resolution
Settable floating-point order
Measurements ADC 24 bit
Ratiometric measurement
Floating-point integer value
The minimum net weight value
Stabilized measurement with noise filter
Measurement / Diagnostics Sensitivity from 1 to 64 mV/V
Thermal drift 25 ppm/K
Interfaces RS485 2 wires speed up to 115.200 bps
Supported protocols ModBUS RTU slave
Data  EEPROM for configuration parameters, retention time 40 years
Connections Removable screw terminals for conductors up to 2.5 mm²
MicroUSB port on the front panel
Programming Plug&Play configurator (EASY SETUP)
Protection degree IP20
Mounting For DIN rail guide 35 mm DIN 46277
Operating temperature  -10..+65°C
Dimension (WxHxD) 17,5x100x112 mm
Weight about 140 g 
Housing Nylon 6 preloaded 30% glass fiber, self-extinguishing class V0
Standards CE
Norms EN 61000-6-4/2002, EN 61000-6-2/2002, EN 61010, EN 60742, IEC 61131

SHIPPING AND EXPORT INFORMATION

PRODUCT CODE Z-SG2
GROSS WEIGHT kg 0.18
ORIGIN IT
CN (Combined Nomenclature) 85389091
ECCN 5A991

Handbücher, Flyer

 
IT EN FR DE ES RU
Technisches Datenblatt
pdf icon it pdf icon en - - - -
System-I/O-Modul Z-PC-line
pdf icon it pdf icon en - - - pdf icon ru
Wandler Signaltrenner Z-Line
pdf icon it pdf icon en - - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es -
User Manual
pdf icon it pdf icon en - - - -
Installation Manual
pdf icon it pdf icon en pdf icon fr pdf icon de pdf icon es -

Tools

 
Z-PC series Labview drivers
zip icon Multi

ZEICHNUNGEN & CAD MODELLE

 
2D model
dwg icon Multi
3D-Modell
stp icon Multi

Zertifizierungen

 
REACH and ROHS declarations
pdf icon Multi
Customs codes
pdf icon Multi
3
0
0

SENECA offices will be closed for Christmas holidays from 24 December to 6 January. Business activities will resume as normal on Monday, 7 January. Orders received from 20 December will be dispatched from Monday, 7 January. We thank you for your cooperation and wish you happy holidays!

Produktversionen

Z-SG2

Strain gauge input Modbus module

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?

Obligatorisches Zubehör, wenn Sie ModBUS-Kommunikation benötigen

Z-PC-DINAL2-17.5

DIN rail bus system head terminal + 2 slots 17.5 mm

Auf Lager ?
Z-PC-DIN2-17.5

DIN rail bus system 2 slots 17.5 mm

Auf Lager ?
Z-PC-DIN8-17.5

DIN rail bus system 8 slot 17.5 mm

Auf Lager ?

Zubehörs

CU-A-MICROB

USB cable plug USB-A - MicroUSB-B - 5P ( KIT - USB , MY2 , Z109REGBP )

Verfügbarkeit zu bestätigen, kontaktieren Sie uns ?
SG-EQ4

Equalization and connection circuit up to 4 load cell in parallel

In begrenzter Menge verfügbar ?